Hot Runners Pages 35 to 48 Troubleshooting “Actual” Hot Runner Controller Temperature By Jim Bott The root cause of a recent part defect was reportedly the deliv-ery of a melt that was too hot. The true root cause, however, was something else entirely. After considering whether the unseated thermocouples were falsely reading air instead of steel and autotuning the exist-ing temperature controller, the company examined the cables. Often, the thermocouple wire will be a K-type instead of the required J-type, but again that was not the case here. However, what was discovered was that the molder was using copper wire. Here is an example to demonstrate why shops should not use copper wire cable to monitor thermocouple feedback to the temperature controller: • Air temperature at (within) the mold electrical junction box (Temperature B): °F • Air temperature at the controller (Temperature A): °F • Setpoint: °F • Using correctly-wired thermocouple (J-type or K-type) exten-sion wire. If the hot end is °F, the Analog Input (AI) terminal block is ºF and the electromotive force (EMF) is “seen” at the AI for any t/c type, then PV = °F -°F + °F = °F. When using t/c wired cable as required, the temperature at the mold electri-cal junction box adds a “zero” unknown error. With copper extension wire, the PV equation remains the Images courtesy of INCOE Corporation. The tip of a thermocouple must be properly seated. same plus an “error” unknown to the operator (or the tem-perature controller). Since the PV equation does not change, neither does the temperature controller’s indicated actual tem-perature. What does exist, but is not indicated, is the “error” that is the actual temperature at the tip of the t/c, which is the added “error” heat to the plastic. If the hot end is °F, the AI terminal block is °F, and the EMF “seen” at the AI is (still) then PV = °F -°F + °F = °F. However, when using copper wire, another junction is added that is not part of the temperature controller logic. The error is not visually indicated on the controller. The t/c-copper junction is at °F (Temperature B): Temperature B (°F) -Temperature A (°F) = °F. The real actual temperature at the tip of the thermocouple is the real temperature of the melt at °F. Again, the real actual temperature is °F because you can-not program the temperature controller with the cold junction and another junction (always a variable). The user has no way of knowing this and trusts the indicated/actual temperature readout on the controller as gospel. Also, the inside temperature of a mold junction electri-cal box mounted on the top side of a mold can experience temperatures well over °F. These temperatures will add and subtract from the unknown error relative to the time of the day and season, which may then impact the temperature within the shop at daytime or nighttime. The bottom line is that you should not use cables with cop-per wire to monitor thermocouple feedback to the tempera-ture controller for any molding application, especially those . with “technical” parts and material. FOR MORE INFORMATION A diagram describing why you should not use cables with copper wire. Air temperature at (within) mold electrical junction box (temperature B) = 100°F; air temperature at controller (temperature A) = 75°F; setpoint is 480°F. INCOE Corporation / 248-556-7857 / INCOE.com/hotrunners Jim Bott, Business Development Manager-Automotive/Heavy Truck 48 Mo MoldMaking g Technology y — — JULY JU 2021 202